14.00.00 TYPE TESTING
14.01.00 The contractor shall furnish the type test reports for
all type tests as per relevant standards and codes as
well as other specific tests indicated in this
specification.
14.01.01(a) Submission of type test results and certificate shall be acceptable provided.
i) The same has been carried out by the bidder/sub-vendor
or exactly the same model/rating of equipment.
ii) There has been no change in the components from the
offered equipment & tested & tested equipment.
iii) The test has been carried out as per the latest
standards along with amendments as on the data of bid
opening.
(b) In case of approved equipment is different from the one
on which the type test had been conducted earlier or any
of the above grounds, then the tests have to be repeated
and the cost of such tests shall be born by the
bidder/sub-vendor within the quoted price and no extra
cost will be payable by the employer on this account.
(c) All Type Tests shall be conducted in National/International
Laboratory only.
(d) Contractor shall submit Type test report as per (a)
Mentioned above or conduct test as per (b) & submit report
For review and approval.
14.01.02 Special Requirement for Solid State Equipments/Systems
The contractor shall submit Type test reports for each
Of the major C&I systems like SG C&I System, TG C&I system,
Station C&I System, Flame Monitoring System, coal feeders
control and instrumentation system, boiler flame analyzing
system, coal bunker level monitoring system, Electronic
remote drum level monitoring system, conductivity type
level switching system,Turbine supervisory system,analyzer
instruments, vibration monitoring systems, Public address
system, PLC for Auxiliary equipment, EPABX etc. shall be as
indicated below :-
i) Surge Protections for Solid State Equipments/ Systems
All solid state systems/ equipments shall be able to
withstand the electrical noise and surges as encountered
in actual service conditions and inherent in a power
plant. All the solid state systems/ equipments shall be
provided with all required protections that needs the
surge withstand capability as defined in ANSI 37.90
a/IEEE-472. Hence, all front end cards which receive
external signals like Analog input & output modules,
binary input & output modules etc. including power
supply, data highway, data links shall be provided with
protections that meet the surge withstand capability as
defined in ANSI 37.90a/ IEEE-472. Complete details of
the features incorporated in electronics systems to meet
this requirement, the relevant tests carried out the
test certificates etc.shall be submitted along with the
proposal. As an alternative to above, suitable class of
IEC-255-4 which is equivalent to ANSI 37.90a/IEEE-472
may also be adopted for SWC test.
ii) Dry Heat Test as per IEC-68-2-2.
iii) Damp Heat Test as per IEC-68-3.
iv) Vibration Test as per IEC-68-2-6.
v) Electrostatic Discharge Tests as per IEC 801-2 or
equivalent.
vi) Radio Frequency Immunity Test as per IEC 801-6 or
equivalent.
vii) Electromagnetic Immunity as per IEC 801-3 or equivalent.
Test listed at item No.v.vi,vii, above are applicable
for front end cards only as defined under item (i) above.