3.00.00 OTHER SG/TG RELATED CONTROL & INSTRUMENTATION
SYSTEM/ EQUIPMENTS
3.01.01 FLAME MONITORING SYSTEM
The purpose of the system is :
i) To detect the individual flame and to enhance the
boiler/furnace safety.
ii) To avoid spurious and unwarranted trips.
iii) To increase operational reliability, availability and
efficiency of the steam generator such that the
consumption of fuel oil shall be reduced to optimal
minimum.
3.01.02 a) Fail Safe easily maintainable flame monitoring System
shall be provided which shall include flame detectors of
proven design for the type of fuel, environmental
condition and other conditions of established
reliability at all loads of the steam generator. It
shall be designed to work under all adverse conditions
such as wide variation in fuel/ air input ratio, wide
variation in fuel characteristics, variation in
operating temperature, maximum temp.under interruption
of cooling air supply.
b) The system shall conform to NFPA recommendation and
location of detectors as per NEC requirements. The detector (photo cell) shall be UV/IR type .Flame detector shall be working on the dynamic and static properties of primary combustion zone of each type of fuel and flicker frequency of flame. It shall pick up only the flame to which it is assigned and shall not respond to the adjacent and background flame or other radiations generated in the furnace. The design shall also take into account the absorption by a coal shroud, recirculated dust or other deposition on the
flame detector head.
c) The complete system shall provide the discrimination
between oil and coal flame intensity indicators for main
flame shall be provided. Also isolated 4-20 A DC
signals shall be provided and looked at DDCMIS.
3.01.03 The system should be easily maintainable and include
automatic self test facility at regular interval. The
Bidder shall also provide a portable flame detector
testing kit with built in stabilizers, capable of
simulating both oil and coal flame, and testing of flame
detector head unit at field. The testing kit shall have
facility for testing all type of electronic cards as
being used in the flame monitoring system.
3.01.04 In case of tangentially fired burner, the bidder shall
arrange flame detectors one in each corner in such a
manner that coal flame detectors are available both
above and below each of the coal elevation and separate
oil flame detectors, one at each corner, for each oil
elevation. In case the Bidder provides discriminating
flame detector capable to detect and discriminate both
oil and coal flame, the same can also be utilized for
monitoring both oil flame in respective elevations and
also the coal flame of adjacent coal elevation. For any
other type of Boiler the flame detectors shall be
provided for each coal and oil burner responding only to
the flame of its associated burner.
Bidder shall also furnish the details of the flame
detector locations and justification for the same.
3.01.05 Site Tests
a)The Bidder shall demonstrate the complete performance of
flame detectors in cold start up test and load condition
test.
In cold start up test, capability of detectors to detect
oil flame under varying oil pressure shall be checked.
In load test, the detector shall be able to detect when
only oil is present, only coal is present and both coal
and oil are present. It shall be ensured that the
detectors are able to detect the proven flame at very
low load with oil GUNS Withdrawn.
The above tests shall be performed for every coal and
oil elevation. Contractor shall submit test results for
review & approval.
3.02.00 Provision of scanner air for cooling the flame detectors
by 100% redundant scanner air fans, one AC and
other DC operated, shall be provided. The emergency and
discharge dampers shall be pneumatically operated with
DC solenoid valves.
3.03.00 GRAVIMETRIC BELT TYPE COAL FEEDERS CONTROL AND INSTRUMENTATION
Bidder shall provide a microprocessor based coal feeder
C&I (explosion proof, meeting NEMA requirements) system
having the following feature. It is preferable to use
the same family of hardware as that of CLCS for implemen-
tation.
1) Bidder shall provide a minimum of two independent speed
sensors, pulsar units and associated amplifiers, etc.for
each of the coal feeders. Output from the speed
sensors will be used to provide at least four 4-20 mA DC
analog signals and any other signals required for the
control of the coal feeder.
In addition, one pulsar unit shall also be provided with
two pulse outputs-one for use in Control system and the
other for remote integrator.
Each coal feeder shall receive signals from DDCMIS for
feeder speed/mill level control. The signal to be
provided by DDCMIS shall be in the form of galvanically
isolated 4-20 mA DC. All required power amplifier
units/interface devices to accept this 4-20 mA signal
shall be included.
2) All associated electronics like buffer amplifiers,
frequency to current converter etc. shall be provided
for each RC feeder with local and remote speed
indicators and integrators. The speed sensors and
pulsar unit shall be totally enclosed, fire, dust and
weather proof, suitable for the service conditions. All
the necessary paddle switches and other detectors to
monitor coal on belt, feeder discharge plugged and other
protection and interlocks for safe operation of the
feeder is to be provided.
3) The control cabinet shall be provided with individual
lights to signal the individual internal trip
conditions. Necessary electronics/ push buttons shall be
provided in the control cabinet for resetting feeders
internal trip. In addition to the internal trips,
there shall be overload trip associated with feeder
motor starter. Provision for resetting the same shall
also be provided. Each feeder shall be provided with a
four position switch located at the feeder for remote,
off, local run (when there is no coal on conveyor)and
calibration purpose.
4) If there is any electronic modules mounted local to the
feeder body then these shall be suitable for operating
in a non air-conditioned area.
5) Coal feeders shall compensate for coal density and feeder volumetric efficiency effects by maintaining coal weight flow to coal burner to match air flow.
3.04.00 ELECTROMATIC SAFETY VALVES
The Electromatic safety valve shall be an automatic,
electrically actuated pressure relief valve. It shall
be possible to set the value for 1% or less differential
between opening and closing pressure. The Electromatic
safety valve shall be provided complete with all
accessories like pressure measuring devices, controller
units, solenoid assembly, impulse piping etc. The
Electromatic safety valves shall be provided with a
local controllers and a miniature remote control station
suitable for mounting on the UCP along with indicating
lights and switches to facilitate auto/remote manual
operation of the valve. The operation of the valve
shall be accomplished by use of a switch or by means of
pressure sensitive element which shall precisely and
automatically relieve the pressures within very close
limits. Bidder shall furnish complete details of the
Electromatic safety valves along with its technical
catalogue, list of accessories etc. In his proposal for
MPPGCL’s approval.
3.05.00 FURNACE TEMPERATURE PROBES
Bidder shall provide 2 Knockoff furnace temp.probes
before platen superheater and/ or before reheater
regions. These furnace temp.probes shall be electrically
operated, fully retractable type. The furnace
temp.probes shall be furnished with complete actuating
mechanism and all the logics required for the actuating
mechanism. The probe shall be provided with position
transmitters, limit switch & indicator for remote
indication. The temp.probe shall have a duplex
thermocouple suitable for the measurement range. Bidder
shall furnish complete details of the temp.probe
alongwith all the technical catalogues including the
details of the actuating mechanism, position transmitters
and limit switch which shall be subject to MPPGCL’s
approval. The logic for the furnace temp.shall
preferably be implemented in the DDCMIS.
3.06.00 BOILER FLAME ANALYSING SYSTEM
To assist in optimization of combustion efficiency with
variation in loads and fuel qualities, betterment in
flame stability and to limit Slagging and unburnt
carbon, NOx level to an acceptable limit through
efficient flame monitoring, analysis and combustion
management system.
The system shall consist of furnace flame cameras(semi
conductor type, one per each coal burner), flame image
processors & a PC based management system, along with
all required accessories. The system shall be capable
to provide information about (i)ignition point position
on fuel stream, (ii)height of fuel steam, (iii) upper
and lower flash point in the combustion area covered by
the corresponding camera as a minimum. Each camera
shall be able to view up to two and half meter or better
of the fuel flow coming from the burner.
The flame image processor shall be housed in a
standalone cabinet to be located in control equipment
room. I shall analyse the images received from each
cameras and shall produce flame parameters every second
in order to provide continuous monitoring of combustion
as well as detection of alarm conditions.
The Pentium PC based management system along with all
required software shall consist of 21″ TFT Monitor PC with
I/O cards, associated keyboard etc. Display of live/frozen flame of the complete furnace as well as live/frozen flame of the selected camera shall be available. The configuration of PC shall be fault tolerant and time synchronized from Master Clock.
The system shall also provide information about average
intensity of the flame, the total intensity of the
analysis area, stability of ignition etc.
The bidder shall provide all hardware and soft wares as
may be required to make the system complete.
The system shall be of proven design and its performance
must be proven for at least two 210 MW rating boilers
using similar type of fuel for a period of two years.
The components to be located at boiler area shall be
able to withstand the stringent environmental condition
expected at such locations with operating boiler.
Adequate cooling arrangement for the cameras and the
components to be located at the furnace area along with
automatic lenses cleaning facility shall be provided.
3.07.00 COAL BUNKER LEVEL MONITORING SYSTEM
Complete Coal Bunker Level Monitoring System consisting
of strain gauge sensors electronic units, bar graph type
displays mounted in Coal Handling Plant Control Room (to
be supplied loose)any necessary intermediate
electronics, interconnecting cables etc. The No.&
location of the strain gauge sensors shall be selected
by the bidder to ensure that overall accuracy (including
sensors & electronic unit)of the system is +/- 10% or
better in spite of possible interaction between support
systems of adjacent bunkers.
The electronic units shall be mounted in a cubicle
located in CER. These shall provide two isolated 4-20 mA DC
output for the bargraph type displays as well as for
DDCMIS.
3.08.00 WATER LEVEL MONITORING SYSTEM
a) Electronic Remote Drum Level Monitoring System
For Boiler drum in order to measure & monitor drum
level, bidder shall provide Electronic Remote Drum Level
Monitoring System working on principle of difference in
electrical conductivity between steam and water. The
monitoring system shall meet the requirements as
indicated below.
(i) Each end of the drum shall have independent pressure
vessels with 16 No. of electrodes covering the
entire range for indication for each end of drum.
Bidder shall provide High & Low and Trip contacts (Very
High, Very Low) with validation and 4-20 mA signal for
Drum level measurement.
(ii) The sensing electrodes shall be placed in equal pitch.
The maximum distance(gap) between two electrodes shall be
50 mm and the electrodes shall be arranged in such a way
that the last and the first electrode shall not be at
any alarm or trip level. In any case, the No.of
electrodes shall not be less than 16 for indication.
(iii) The system shall be proven and approved by Factory
mutual, USA of equivalent, IBR etc.
3.09.00 Conductivity Type Level Switching System
3.09.01 For Deaerator, Condenser hotwell and HP & LP
heaters alarms/protections, level switching systems
employing conductivity probes shall be provided. Each of
the switching systems shall be furnished complete with
at least 4 Nos. conductivity probes column for mounting
the conductivity probes, isolating valves, drain valves
vent valves, electronic units, twisted & shielded pair
interconnecting cables. The conductivity probes & the
column for mounting these probes shall be designed for
the respective pressure and temp.conditions.
The electrodes shall be designed in such a manner that
they sense the rising water level and that they do not
give faulty indication due to falling condensate on the
electrodes. Also, each system shall incorporate proper
validation circuits that eliminate spurious or unwanted
alarm/ trip actions due to a single channel fault.
3.09.02 Bidder shall provide Conductivity type level switches in
drain pots of MS, HRH, CRH pipes etc. as per ASME TDP-1.
3.10.00 TURBINE SUPERVISORY SYSTEM (TSS)
3.10 01 The Turbine supervisory equipment shall be complete
including sensors, transmitters, converters, limit value
monitors, measuring and amplifier modules, power
supplies etc.with the required accessories including
twisted and shielded instrumentation cables,
compensating cables, junction boxes etc. Following
measurements shall be provided as minimum.
i) Shaft Eccentricity Detection
ii) Absolute as well as relative shaft vibration
measurement, of each bearing in both X & Y direction.
iii) Differential expansion of rotor and cylinder for HPT,
IPT and LPT and LPT.
iv) Over all expansion of HPT and IPT.
v) Absolute bearing vibration measurement of each bearing
in both X & Y directions.
vi) Stator winding vibration vibration measurement in radial
and tangential directions.
vii) Axial shift of the rotor
viii) Turbine Speed
ix) Emergency stop and control valve position
x) Main Steam and Hot Reheat Steam Inlet Temp. and Pressure
xi) Bearing metal and drain oil Temp.
xii) Turbine metal Temp.
xiii) In case of vibration, shaft mounted reference detectors
and required supervisory instrument circuitry shall also
be provided.
xiv) Any other measurement recommended by the Turbine
manufacturer or required for the safe and reliable
operation.
The system shall be provided with suitable hardware for
necessary signal processing. The system should be
capable of signal distribution and interfacing with
other Control Systems. The system should suitably
interface with MMIPIS system supplied by bidder.
3.10.02 For all vibration measurements indicated in
items(ii)and(v)v.z.absolute bearing vibration relative
shaft vibration and absolute shaft vibration as
indicated under Clause 3.9.01 above, redundant
microprocessor/fault tolerant computer based system and time synchronized from Master Clock shall also be
provided to achieve the following functions :-
(i) On line spectrum/harmonic analysis.
(ii) Identification of the exact nature of failure resulting
in increase in bearing vibration and direct message on
the CRT indicating the exact nature of fault
e.g.Misc.shaft crack bearing looseness etc.
(iii) Storage and comparative analysis of vibrations.
(iv) Generation/ analysis of Bode Plot/Orbit Plot and time
waveform/ nyquist plot/ shaft center like plat/
cascade and water fall plot.
All the vibration parameters as well as Turbine
supervisory parameters shall also be fed to the DCS
through hardwiring so that all these parameters are
suitably displayed on the OWS. All required I/O cards and
other processing modules etc. shall be provided for this
purpose.
3.10.03 Test calibration jigs for site calibration of all
sensors of TSS shall be provided. Telephone jacks
shall be incorporated in all the TSS cubicles for
communication during site calibration etc.
3.10.04 Environmental limits for Turbine Turbovisory
instruments.
a) Operating Temperature for sensor and Extension cable.
0 – 177 Deg.C
b) Relative Humidity - 0- 95%
c) Corrosion Resistance
Probe Operation shall not effected by direct contact
with water or lub oil.
d) Sensor to Junction box extension cable shall be FRLS,
screened, armoured, twisted, oil resistant.
e) The system shall be designed accordance to
recommendation of API-670.
3.11.00 The configuration of all PC shall be fault tolerant and
Time synchronized with master clock.
![Almost Like Another Planet... Pamukkale Blues (UNESCO World Heritage) [Explore #1, THANK YOU] Almost Like Another Planet... Pamukkale Blues (UNESCO World Heritage) [Explore #1, THANK YOU]](http://static.flickr.com/7079/7209710670_f67079c754_t.jpg)
[...] 3.OTHER SG/TG RELATED CONTROL & INST [...]
[...] 3.OTHER SG/TG RELATED CONTROL & INST [...]