15.00.00 ELECTRICAL ACTUATORS
15.01.00 Type
The electrical actuators shall be non integral type.
15.02.00 Rating
a) Supply Voltage & frequency – 415 V +/- 10%, 3 phase, 3
wire 50 Hz +/- 5%.
b) Sizing – For OPEN/CLOSE at rated speed against designed
Diff.pressure at 90% of rated voltage.
c) For isolating services – 60 starts/ Hr.
d) For Modulating Services – 1200 Starts/ Hr.
15.03.00 Construction
a) Enclosure – Totally enclosed weatherproof Min.IP-67 Deg.
of protection.
b) Gear Train- Metal (Fiber gears are not acceptable)self
locking to prevent drift under torque
switch(where ever applicable)spring pressure
when motor is de-energized.
c) Manual Wheel- Shall disengage automatically during motor
operation.
15.04.00 Motor
a) Type - Squirrel cage induction motor, direct on line
starting with starting current limited to six times the
rated current as per IS 325.
b) Enclosure – Totally enclosed, self ventilated IP-67 Deg.
of protection.
For Minus Level – IP-68
c) Insulation
All Motor of Electrical Actuator shall be `F’ Class
Insulation. Temp. rise upto `B’ Class.
d) Bearings
Double shielded, grease lubricated antifriction.
e) Earth Terminals – Two
f) Protection
i) single phasing protection
ii) Over heating protection through thermostat- 3 No.
(One in each winding)
iii) Wrong phase sequence protection
15.05.00 Position/ Torque Switches
i) Limit Switches - 4 Nos.(2 NO + 2NC)
ii) Torque Switches - 2 Nos.(2 NO + 2NC)
iii) Rating of Switches - 5 A,240 V AC or 0.5 A, 220 VDC
15.06.00 Local Operation
It shall be possible to operate actuator locally.
Lockable local/ remote selection shall be provided on
actuator.
15.07.00 Position Indicator - To be provided.
15.08.00 Position Transmitter(For Modulating/Inching Type)
As required. Suitable for stabilized 4-20 mA signal, 2
wire inductive type, 24 volts DC operated.
15.09.00 Wiring
Suitable voltage grade copper wire.
15.10.00 Terminal Box
i) Pin plug and socket type.
ii) Necessary glands for power cables shall be provided.
15.11.00 Colour shade of Actuator – BLUE(RAL 5012)
15.12.00 Admissible Ambient Temp. – 0-80 Deg.C
15.13.00 Bidder shall provide lockable emergency PB near
Electrical Actuator and stop PB shall be wired directly to MCC.